ARMY TM 9-6115-641-24
AIR FORCE TO 35 C2-3-456-12
2-21-2. Removal.
a. Shut down generator set.
b.
Open left side engine access door and disconnect negative battery cable.
c.
Open storage box access door and uncouple three harness connectors on bottom of control box.
d. Remove control box top panel, paragraph 2-16-1.
e. Remove nuts (1, Figure 2-10), Iockwashers (2), washers (3), and voltage reconnection switch knob (4).
f.
Remove bolts (5), nuts (6), and door striker (7).
g.
Remove control box assembly (8).
2-21-3. Repair.
Repair control box by replacing terminals, screws, bolts, and components.
2-21-4. Installation.
a.
Install control box assembly (8, Figure 2-10) and door striker (7) and secure with bolts (5), and nuts (6).
b. Install voltage reconnection switch knob (4), washers (3), Iockwashers (2), and nuts (1).
c.
Install control box top panel, paragraph 2-16-4.
d. Connect three wiring harness connectors and close storage box access door.
e.
Connect negative battery cable. Close engine access door.
2-22.
CONVENIENCE RECEPTACLE.
NOTE
Applicable to MEP-802A only.
2-22-1. Inspection.
a.
Shut down generator set.
b.
Release control panel by turning two fasteners and lower control panel slowly.
c.
Inspect CONVENIENCE RECEPTACLE for cracks, breaks, corrosion, and other damage.
d.
Raise and secure control panel.
2-22-2. Testing.
a.
Shut down generator set.
b. Remove control box top panel, paragraph 2-16-1.
c.
Tag and disconnect CONVENIENCE RECEPTACLE (5, Figure 2-11) electrical leads.
d.
Set multimeter for ohms and check for continuity between upper and lower side terminals of each plug outlet.
e.
Replace CONVENIENCE RECEPTACLE if continuity is indicated between terminals.
f.
Connect electrical leads to receptacle (5) and remove tags.
g.
Install control box top panel, paragraph 2-16-4.