ARMY TM 9-6115-641-24
AIR FORCE TO 35C2-3-456-12
2-22-3. Removal.
a.
Shut down generator set.
b.
Open left side engine access door and disconnect negative battery cable.
c.
Remove control box top panel, paragraph 2-16-1.
d. Tag and disconnect CONVENIENCE RECEPTACLE (5, Figure 2-11) electrical leads.
e. Remove screws (1, Figure 2-11), nuts (2), and cover (3).
f.
Remove machine screws (4) and CONVENIENCE RECEPTACLE (5) from control box.
2-22-4. Installation.
a. Install CONVENIENCE RECEPTACLE (5, Figure 2-11) and secure with machine screws (4).
b.
Install CONVENIENCE RECEPTACLE cover (3) with screws (1) and nuts (2).
c.
Connect electrical leads and remove tags.
d.
Install control box top panel, paragraph 2-16-4.
e.
Connect negative battery cable and close access door.
2-23.
GROUND FAULT CIRCUIT INTERRUPTER.
NOTE
Applicable to MEP802A only.
2-23-1. Inspection.
a.
Shut down generator set.
b.
Release control panel by turning two fasteners and lower control panel slowly.
c.
Inspect GROUND FAULT CIRCUIT INTERRUPTER for cracks, loose mounting, frayed wires, and other
damage.
d.
Raise and secure control panel.
2-23-2. Testing.
a.
Start and operate generator set at rated voltage and frequency.
b.
Press TEST button on GROUND FAULT CIRCUIT INTERRUPTER.
c.
Set multimeter for AC voltage and check for zero voltage at CONVENIENCE RECEPTACLE.
d.
Press RESET button on GROUND FAULT CIRCUIT INTERRUPTER and check for 120 VAC at CON-
VENIENCE RECEPTACLE.
e.
If indications are other than above, replace GROUND FAULT CIRCUIT INTERRUPTER.
2-23-3. Removal.
a.
Shut down generator set.
b.
Open left side engine access door and disconnect negative battery cable.
c.
Remove control box top panel, paragraph 2-16-1.
d.
Tag and disconnect CIRCUIT INTERRUPTER (8, Figure 2-11) electrical leads.
e.
Remove screws (6), nuts (7), and GROUND FAULT CIRCUIT INTERRUPTER (8) from malfunction indicator
panel (12).
2-50