ARMY TM 9-6115-641-10
AIR FORCE TO 35C2-3-456-11
2-6 PMCS PROCEDURES - Continued.
TABLE 2-4. Operator Preventive Maintenance Checks and Services - Continued
Location
Not Fully
Item
Item to
Mission
No.
Interval
Check/Service
Procedure
Capable if:
WARNING
The fuels used in this generator set
are highly explosive. DO NOT
smoke or use open flame when
performing maintenance. Flames
and explosion can occur resulting
in severe injury or death.
33
After
Engine
Inspect for loose, damaged, or missing
Loose, damaged,
Assembly
hardware.
or missing hard-
ware.
34
After
Fuel System
Inspect for leaks, damage, loose, or
Any fuel leaks,
missing hardware.
damage, loose or
missing parts.
35
After
Fuel Filter/
Inspect for leaks, cracks, damage,
Any fuel leaks.
Water
proper mounting, loose or missing parts.
Separator
Drain water.
Water not drained.
36
After
Lubrication
Inspect for leaks, damage, loose or
Class III leaks,
System
missing parts.
damage, loose or
missing parts.
Inspect oil level.
Oil level is low.
Inspect for contamination.
Oil shows signs of
contamination.
Cooling System.
WARNING
Cooling system operates at high
temperatures. Personal injury or
death from burns or scalding can
result from contact with high pressure
steam and/or liquid.
37
After
Radiator
Inspect for leaks, damage, loose or
Class III leaks or
missing parts.
missing radiator
cap.
38
After
Hoses
Inspect for leaks, cracks, or missing
Class III leaks or
parts.
missing clamps or
hoses.
39
After
Fan Bet
Inspect for cracks fraying, or
Broken or missing
looseness.
belt.
Control Box
Assembly
40
After
Controls and
Inspect for damaged or missing parts.
Damaged or mis-
Indicators
ing parts.
2-15