TABLE 2-4. Operator Preventive Maintenance Checks and Services - Continued
Item
Number
26
27
28
29
30
31
32
Interval
During
During
During
During
After
After
After
Location
Item to be
Check/Service
Cooling
System
Cooling Fan
Overflow
Bottle
Grounding
Rod Assembly
Ground Rod
Cable and
Connections
Control Box
Assembly
Controls and
Indicators
Generator Set
Exterior
Housing
Identification
Plates
Skid Base
Procedure
Inspect for obstruction, damage, or
looseness.
Inspect for unusual noise in fan area.
Inspect for proper mounting, leaks,
or missing hardware.
Inspect for damage, corrosion, and
loose connections.
High voltage is produced when this
generator set is in operation.
Personal injury or death due to
electrocution could result.
Inspect indicators are operating
properly.
NOTE
If The equipment must be kept in
service continuous operation,
check and only those items that can
be checked and serviced without
disrupting operations. Complete
all checks and services when
equipment is shut down.
Check door panels, hinges, and
latches for damage, loose, or
corroded items.
Check to ensure identification plates
are secure
Inspect skid base for cracks and/or
corrosion.
Not Fully Mission
Capable if:
Damaged or loose.
Unusual noise
from area.
Class III leaks or
missing hardware,
Damaged, cor-
roded, or loose
connections.
Indicators are
not operating
properly.
Cannot secure
door.
Skid base is
cracked or shows
signs of structural
damage.
2-14