ARMY TM 9-6115-641-10
AIR FORCE TO 35C2-3-456-11
NOTE
The generator set can be operated continuously at anyload from no load up to and
including rated load; However, at light loads (less than 25% of set rating) an oily residue
(unburned fuel oil) may occasionally be noticed in the exhaust system outlet and around
connection joints in the exhaust system. This residue is caused by the inability of the
fuel injection system to consistently meter the small amount of fuel required to operate at
these low load levels and is not a defect in the fuel system. The oily residue could affect
engine performance and create a cosmetic problem on and around the generator set.
Operation at rated load will burn off this oily residue. The length of time required at rated
load depends on the amount of residue. The muffler may also need to be removed and
cleaned if excessive build up occurs. This oily residue can be prevented by increasing
the electrical load on the set.
2-6 PMCS PROCEDURES .
Table 2-4. Operator Preventive Maintenance Checks and Services
Item
Number
1
2
3
4
Interval
Before
Before
Before
Before
Location
Item to be
Check/Service
Generator Set Ex-
terlor
Housing
Identification
Plates
Skid Base
Acoustical Materi-
als
Engine Assembly
Procedure
NOTE
If the equipment must be kept
in
continuous
operation,
check and service only those
items that can be checked
and serviced without disrupt-
ing operations. Complete all
checks and services when
equipment is shut down.
Check door panels, hinges, and latches for
damage, loose, or corroded items.
Inspect air intake and exhaust grills for de-
bris.
Check to ensure identification plates are
secure.
Inspect skid base for cracks and/or are cor-
rosion.
inspect to ensure acoustical materials, lo-
cated in the grill areas and under the en-
gine, are secure, damaged, or missing.
WARNING
With any access door open
while the generator set is in
operation, the noise level
may cause hearing damage.
To avoid hearing damage,
hearing protection should be
worn.
Not Fully Mission
Capable if:
Cannot secure door.
Skid base is cracked
or shows signs of
structural damage.
Change 1 2-9