ARMY TM 9-6115-641-10
AIR FORCE TO 35C2-3-456-11
Table 2-2. Malfunction Indicator Panel
Key
Control or Indicator
Function
1
NO FUEL indicator
Lights when fuel level in fuel tank
is below preset level.
2
COOLANT HIGH TEMP
Lights when engine coolant
indicator
temperature exceeds 225° ± 5° F
(107° ± 3° F).
3
OVERVOLTAGE indicator
Lights when voltage in 120 volt
generator coil exceeds 153 ± 3
volts.
4
PUSH TEST RESET LAMPS
Tests and resets fault indicator
lamps.
5
OVER LOAD indicator
Lights when current in any phase
exceeds 110 percent of rated current.
6
GROUND FAULT CIRCUIT
Tests Ground Fault Circuit
INTERRUPTER TEST
Interrupter.
pushbutton
7
Ground Fault Circuit
Mechanically trips red indicator, at
Interrupter indicator
ground fault condition in circuit of
convenience receptacle.
8
Ground Fault Circuit
Depress to reset Ground Fault Circuit
Interrupter PUSH TO
Interrupter after test or ground
TEST Pushbutton
fault has occurred.
9
SHORT CIRCUIT indicator
Lights when generator set output in
any phase exceeds 425 ± 25 percent
of rated current.
10
LOW OIL PRESSURE
Lights when engine lubrication
indicator
systems pressure is less than 15 ± 3
psi (103.4 ± 20.7 kPa) during engine
operation.
11
Convenience Receptacle
Circuit breaker trips on when load
Overload Circuit
on convenience receptacle exceeds 10
Breaker (10-amp in-line
amps (fuse blows on generator sets,
fuse on generator sets,
contract number DAAK01-88-D-D080).
contract number DAAK01-
88-D-D080)
2-6 Change 2