TM 55-6115-491-40
Figure 4-5. PM Generator Full-load Voltage Test.
about five minutes to allow the temperature to stabilize.
the DC output. It shall be as shown in C, figure 4-6. If a
c. With the generator operating at 7, 000 RPM,
check the DC output voltage. It shall be 19.0 volts
minimum.
Figure 4-6. Waveforms Produced by PM Generator Output.
4-12. AC Generator Phase Rotation Test.
balanced 3-phase load, and 0.75 power factor. Voltage
a. Operate the generator at 8, 000 RPM no load,
regulator and control panel are to be connected to
driving the rotor in a counterclockwise direction, facing
b. Operate generator under these conditions
drive end.
b. With a phase sequence indicator connected
until the AC stator stack temperature does not increase
more than 2 F (1.1 C I in five minutes. Record line
to the generator output terminals as shown in figure 4-2,
voltages and current, exciter armature voltages and field
the phase rotation sequence shall be T1, T2 T3
current, air inlet temperature,
AC stator stack
4-13. HEATING, COMMUTATION, AND SYMMETRY
temperature and commutation. Cummutation shall be
OF CONSTRUCTION TEST .
such that there is no more than pin point arcing along the
a. Using a suitable clamp, attach thermocouple
edges of the brushes. AC stator stack temperature shall
to generator housing. With cooling air supplied in
not exceed 3250 F (1630 C). Exciter field current shall
be 0.75 ampere maximum. KVAR shall be 13.25 F0.75.
determining speed within : 1 percent, operate generator
KW shall be 15.0 : 0.75.
at 8, 000 : 80 RPM, 208 volts, 55.5 amperes with
c. For symmetry of construction, determine
unbalance which is defined as 100 times the
4-5