TB 11-6115-741-24
APPENDIX C (continued)
TIER 1 TECHNICAL INSPECTION CHECKLIST
Tier 1 Technical Inspection
Condition
Inspect fuel pumps (main and auxiliary as
applicable) for loose connections, broken wires,
49
missing components, clogged filters, clogged
screens, and cracked intake and output lines.
50
Inspect 5 & 10 kW TQG battery charging
voltage regulator. Open DC breaker, disconnect
battery negative cable, set meter to read DC
amps, measure DC amps between cable and neg.
battery terminal. Reading < 5 milliamps is OK.
51
If applicable, inspect breather heating elements
for broken wires and missing insulation.
Inspect switchbox assembly for damage,
corrosion, missing components, loose screws and
connectors, damaged wiring harness, broken
52
wires, burned out light bulbs, stripped terminal
lug threads, and missing terminal lug nut
retainers.
Inspect power plant cables between switchbox
53
insulation, broken wires, damaged connectors,
kinks, or signs of overheating.
Ensure that the safety switches are wired
54
correctly.
55
Inspect all mounts for cracking, tears, being
On the 3 KW TQG, verify that the bolts and
56
flat/lock washers are installed on the muffler
bracket.
57
Inspect ASKs for missing or damaged hardware,
nuts, bolts, clamps, door, panels, and
58
components. Inspect ASKs for rust, corrosion,
and holes that go completely through the panels.
Inspect the switch box interior and exterior for
59
missing and damaged panels, hardware,
components, and wiring as applicable.
On the 5 & 10 KW TQG, inspect the feet on the
60
stator housing for cracks.
Mil Std Generator Specific Inspections
61
62
Inspect Static exciter and voltage regulator for
sand and dust accumulation.
C-4