TM 9-6150-228-13&P
Table 2-2. Typical User Requirements
Receptacle
Total
amps
120V/1ph
208V/3-ph
Total
Item
plug
class L
kilowatts
1-ph
3-ph
Tent No. 1
1. Electric drill
1
0.800
6.6
6.6
120 V1800 W
2. Electric grinder
1
0.900
7.5
120 V/900 W
3.Sander
1
0.450
3.75
120 V/450 W
4.Radi0 Set
1
0.180
1.5
120 V/180 W
5 Lights
6
0.360
3.0
120 V/60 W (6 ea)
6. Welder
1
1.600
4.5
208 V/3-ph/600 W
Total for Tent No. 1
10
1
4.290
22.35
4.5
Tent No. 2
1. Electric heater
1
1.300
10.8
120 V/1300 W
2. Radi0 transceiver
1
1.000
8.3
120 V/1000 W
3 Light set
1
0.360
3.0
120 V/60 W (6 ea)
Total for Tent No. 2
3
2.660
22.1
Tent N0.3
1. X-ray unit
1
0.600
5.0
120 V/600 W
2. Film pr0cess0r
1
0.120
1.0
120 Vf20 W
3. Sucfi0n unit
1
0.140
1.2
120 V/140 W
4. Pr0phylaxis unit
1
0.150
1.3
120V150 W
5. Surgery lamp
1
1.200
10.0
120 V/1200 W
6. Light Set
1
0.480
4.0
120 V/60 W (8 ea)
Total for Tent No. 3
6
2.690
22.5
Total Requirements
19
1
9.640
67.0
4.5
2-8