TM 9-6150-228-13&P
2.5.2.
Operation. Advise users that power distribution panel is operational.
2.5.3.
Resetting the Circuit Breakers.
2.5.3.1
A circuit breaker in the tripped position (midway between ON and OFF positions) indicates the circuit breaker
has been subjected to an overload condition. Wait 2 minutes before resetting the circuit breaker. To reset the circuit
breaker, move the switch to the OFF position and then to the ON position.
2.5.3.2
If the circuit breaker trips again after resetting, the overload or fault must be cleared before safe operation
can be resumed. If no fault or overload condition is detected, troubleshoot the electrical circuit (Table 3-1).
2.5.3.3
A circuit breaker in the OFF position indicates the circuit breaker has not been operated.
2.5.4.
Shutdown Procedures.
2.5.4.1
Shut down user's equipment.
2.5.4.2
Set individual branch circuit breakers to OFF position.
2.5.4.3
Set both MAIN 1 and MAIN 2 circuit breakers to OFF position.
2.5.4.4
Refer to applicable technical manuals and shut down the generator set.
2.6 DECALSAND INSTRUCTON PLATES (FIGURE2-6). The decals and instruction plates are affixed to the power
distribution panel at various locations. These plates and decals provide information, instructions, identification, and
connections for operating and maintaining the power distribution panel. These decals and plates are shown individually
following the locator views.
LEGEND
1.
Information Plate, WIRING DIAGRAM 100 KW POWER DISTRIBUTION PANEL.
2.
Decal Strip, Circuit Breakers 3, 5, 7, 9, 11, 13 and 15.
3.
Decal Strip, Circuit Breakers 4, 6, 8, 10,12, 14 and 16.
4.
Decal Strip, connectors, nine 60 Amps, eleven 60 Amps, thirteen 60 Amps, fifteen 60 Amps.
5.
Information Plate, Manufacturer's Nameplate.
6.
Decal Strip, connectors three 1 00 Amps, five 1 00 Amps, seven 60 Amps.
7.
Information Decal, Circuit Breaker MAIN one 400 AMPS 30.
8.
Information Decal, INPUT LINE 1 TERMINAL BLOCKS INSIDE.
9.
Information Decal, WARNING LETHAL VOLTAGES PRESENT.
10. Information Decal, 120/208 VOLTS.
11. Information Decal, INTERLOCK OPERATION.
12. Information Decal, Circuit Breaker MAIN two 400 AMPS 30.
13. Decal Strip, A B C.
14. Decal Strip, connectors eight 60 Amps, six 1 00 Amps, four 1 00 Amps.
15. Decal Strip, connectors sixteen 60 Amps, fourteen 60 Amps, twelve 60 Amps, ten 60 Amps.
16. Information Decal, Fork Lift.
17. Information Decal, TERMINAL BLOCK LAYOUT (Inside Access Door).
18. Information Decal, INPUT LINE 2 TERMINAL BLOCKS INSIDE.
19. Information Decal, GROUND.
2-12