TM 9-6150-228-13&P
Table 2-1. Operator Preventive maintenance Checks and Services for Model PEU-155/E
Item
No.
Interval
Location
Item to
Check/Service
Procedure
Not fully Mission
Capable If:
1
Before
Enclosure
Inspect for obvious damage to endosure or door
assemblies
Intemal wiring is
exposed
2
Before
Endosure
Inspect cover assembly induding hinge and gasket.
Cover will not close
properly.
3
Before
Endosure
Check drainage openings in endosure lower comers
and dean if necessary.
4
Before
Top Panel
Check for damaged circuit breakers
Circuit breakers are
damaged so as to
affect function or
safety.
5
Before
Top Panel
Check operation of sliding bar assembly
Sliding bar is damaged
so that it will not
function properly.
6
Before
Top Panel
Check that indicator lights are present and unbroken.
7
Before
Connectors
Inspect connectors for damage
Connectors are
damaged
8
Before
Connectors
Inspect connector covers
Covers or gaskets are
missing or
unserviceable.
9
Before
Cable
assemblies
Check for damaged cable connectors
Cable connectors are
darnaged
10
Before
Cable assemblies
Check for split, cut, and damaged insulation.
Bare wires are
exposed.
11
Before
Ground wires
Check that ground wires are securely attached to
ground terminal(s).
Ground wires are
frayed or missing
12
Before
Connectors
Check that unused connectors are capped.
CAUTION
When input power is energized, all 3-phase
indicator lights should illuminate. If all three
lights are not illuminated, immediately turn off
the input power and notify the next higher level
of maintenance. Damage to the equipment
being energized may occur if the problem is not
corrected.
Maintenance
personnel
should
consult the troubleshooting chart, Table 3-1, to
determine the problem.
2-5