TM 9-6115-730-24
UNIT (FIELD) LEVEL MAINTENANCE
TACTICAL QUIET GENERATOR 200 kW, 50/60 Hz MEP-809A/PU-809A
CONTROL BOX DOOR ASSEMBLY MAINTENANCE
INITIAL SETUP:
Tools and Special Tools
Personnel Required
Tool Kit, General Mechanic's (WP 0123, Item 1)
One
References
TM 9-6115-730-24P
WARNINGS
Metal jewelry will conduct electricity. All jewelry can become entangled in generator set
components. Remove all jewelry when working on generator set. Failure to comply can cause
injury or death to personnel by electrocution.
DO NOT wear loose clothing when performing checks, services and maintenance. Failure to
comply can cause injury or death to personnel.
High voltage is produced when this generator set is in operation. Make sure unit is completely shut
down and free of any power source before attempting any repair or maintenance on the unit.
Failure to comply can cause injury or death to personnel.
High voltage is produced when the generator set is in operation. Never attempt to start or
maintain the generator set unless it is properly grounded. Failure to comply can cause injury or
death to personnel.
REMOVAL
1. Turn two latches (Figure 1, Item 1) and open control box door (Figure 1, Item 2).
2. Remove eight lockwashers (Figure 1, Item 3), washers (Figure 1, Item 4), screws (Figure 1, Item 5), and
control box door (Figure 1, Item 2).
END OF TASK
DISASSEMBLY
1. Remove eight nuts (Figure 1, Item 6), screws (Figure 1, Item 7), and two latches (Figure 1, Item 1).
2. Remove eight locknuts (Figure 1, Item 8), screws (Figure 1, Item 9), and hinge (Figure 1, Item 10).
END OF TASK
0020-1