REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
FACTORY
DESCRIPTION
RANGE OF VALUES
SETPOINTS
DEFAULT
SP01 Spare Input 1 Active State: Input
0 Active low
0
0
state used by GSC to declare that SP01
1 Active high
fault exists.
SP02 Spare Input 1 Response: GSC
0 Shutdown
0
0
response to SP01 fault.
1 Alarm
SP03 Spare Input 1 Time Delay:
0 to 250 seconds in
0 seconds
1 seconds
Amount of time GSC waits before
increments of 1
responding to a SP01 fault.
SP04 Spare Input 2 Active State: Input
0 Active low
0
1
stated used by GSC to declare that
1 Active high
SP02 fault exists.
SP05 Spare Input 2 Response: GSC
0 Shutdown
0
0
response to SP02 fault.
1 Alarm
SP06 Spare Input 2 Time Delay:
0 to 250 seconds in
0 seconds
0 seconds
Amount of time GSC waits before
increments of 1
responding to SP02 fault.
SP07 Spare Input 3 Active State: Input
0 Active low
0
0
state used by GSC to declare that SP03
1 Active high
fault exists.
SP08 Spare Input 3 Response: GSC
0 Shutdown
0
0
response to SP03 fault.
1 Alarm
SP09 Spare Input 3 Time Delay:
0 to 250 seconds in
0 seconds
0 seconds
Amount of time GSC waits before
increments of 1
responding to SP03 fault.
SP10 Spare Input 4 Active State: Input
0 Active low
0
0
state used by GSC to declare that SP04
1 Active high
fault exists.
SP11 Spare Input 4 Response: GSC
0 Shutdown
0
0
response to SP04 fault.
1 Alarm