TM 9-6115-729-24
0085
REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
Table 5. OP5-1 Protective Relaying Setpoint Programming - Continued.
FACTORY
SETPOINTS
60 Hz (50 Hz) 3
DESCRIPTION
RANGE OF VALUES
DEFAULT
0 through 30 seconds 2 in
P127 Generator Reverse Power
10 sec
3 sec
Shutdown Time Delay: Amount of time
increments of 1
the FSC+ waits before issuing a reverse
power shutdown.
0 disabled
1
1
Enable: GSC enables or disables the
1 enabled
overcurrent alarm.
100 through 160% of
105%
160%
Alarm Threshold: Level of current GSC
nameplate current in
uses to issue a phase overcurrent alarm.
increments of 5%
0 through 250 seconds 2 in
0 sec
0 sec
Alarm Time Delay: Amount of time GSC
increments of 1
waits before issuing a phase overcurrent
alarm.
P131 Generator Total Overcurrent
100 through 160% of
105%
160%
Alarm Threshold: Level of current GSC
nameplate current in
uses to issue a total overcurrent alarm.
increments of 5%
0 through 250 seconds 2 in
P132 Generator Total Overcurrent
0 sec
0 sec
Alarm Time Delay: Amount of time GSC
increments of 1
waits before issuing a total overcurrent
alarm.
0 disabled
1
0
Enable: GSC enables or disables the
1 enabled
overcurrent shutdown.
100 through 160% in
110%
160%
Shutdown Threshold: Level of current
increments of 5%
GSC uses to issue a phase overcurrent
shutdown.
0 through 500 seconds 2 in
0 sec
0 sec
Shutdown Time Delay: Amount of time
increments of 1
GSC waits before issuing a phase
overcurrent shutdown.
____________
2
When programmed to 0 seconds, the actual time is from 0.5 to 1.0 seconds.
3
Setpoints to be changed from factory defaults to 100 TQG setpoints at switch gear supplier.
0085-22