REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
Table 4. 100 kW OP5-0 Engine/Generator Setpoint Programming - Continued.
120/208
240/416
FACTORY
60Hz
60 Hz
(50 Hz) 8
(50 Hz)
DESCRIPTION
RANGE OF VALUES
DEFAULT
0 to 20 seconds in increments of
5 sec
5 sec
5 sec
P024 Crank Time Delay:
1 second
Amount of time GSC delays
activation of the fuel control
relay (FCR) during a crank
cycle. This setpoint is for gas
engines only. The P024
setpoint only functions when
the P023 setpoint is set to 1
(gas engine). 7
P025 Oil Temperature
0 for TQGs without an oil
0
0
0
Sensor Installed: Tells
temperature sensor
whether or not the optional
1 for TQGs with an oil
engine oil temperature sensor
temperature sensor
is installed on the TQG.
P026 High Oil Temperature
85 to 123C (185 to 253F) in
107C
253F
253F
Shutdown: Oil temperature
increments of 1
(225F)
used by GSC to declare a high
oil temperature shutdown fault
exists (after a 10 second
delay). Refer to the panel
model number.
P027 Shutdown Override for
0 for alarm only (shutdown
0
0
0
High Oil Temperature Fault:
override, no engine shutdown)
GSC+ response to an engine
1 for engine shutdown
high oil temperature fault.
P028 Nameplate Voltage:
100 to 25kV in increments of 1
480V
416V
208V
(416V)
(208V)
This setpoint is used for
protective relaying functions.
P029 Nameplate Current:
0 to 4000 A in increments of 1
600A
173A
347A
Rated current output of
(144A)
(288A)
generator.
____________
7
The P024 setpoint only functions when the P023 setpoints is set to 1 (gas engine).
8
Setpoints to be changed from factory defaults to 100 TQG setpoint at switch gear supplier.