TM 9-6115-729-24
0085
REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
Table 7. OP6 Spare Input/Output Setpoint Programming - Continued.
FACTORY
DESCRIPTION
RANGE OF VALUES
SETPOINTS
DEFAULT
SP12 Spare Input 4 Time Delay:
0 to 250 seconds in
0 seconds
0 seconds
Amount of time GSC waits before
increments of 1
responding to SP04 fault.
SP13 Spare Output Response: GSC
0 Active low
0
0
response to the spare output trigger
1 Active high
condition.
SP15 Spare Relay Output Response:
0 Relay inactive when
1
1
GSC response to the spare relay trigger
triggered
condition.
1 Relay active when
triggered
SP14 Spare Output Trigger Condition:
8
0 Unused
8
1 Active SP01 fault 2
The condition used by GSC to trigger the
2 Active SP02 fault 2
spare output trigger response.
3 Active SP03 fault 2
4 Active SP04 fault 2
5 Any combination
of active SP01,
SP02, SP03, or
SP04 faults 2
6 Any active shutdown
fault (AL1 thru AL14,
SP01 SP04, or
CID FMI)
8
12
SP16 Spare Relay Output Trigger
7 Any active alarm
Condition: The condition used by GSC
or shutdown fault
to trigger the spare relay.
(AL1 thru AL15, SP01 thru
SP04, or CID FMI)
8 Cooldown mode
2
9 Coolant loss fault
10 High oil temperature
fault 2
11 CCM control 2
12 Other protective relay
____________
2
Either alarm or shutdown faults are valid trigger conditions.
0085-27