ARMY TM 9-6115-673-13&P
AIR FORCE TO 35C2-3-512-1
(3) Set multimeter for AC volts and connect to VOLTS AC meter terminals 1 and 2.
WARNING
High voltage is produced when this generator set is in
operation. Use care when working around an open control
panel with the generator set operating. Improper operation
and/or failure to follow this warning could result in personal
injury or death by electrocution.
(4) Start and operate generator set at rated voltage. Record multimeter indication.
(5) Shut down generator set.
(6) Replace VOLTS AC meter if multimeter indicates AC voltage within rated range
(114-126 VAC) and meter does not.
(7) Install gauge protective cover.
(8) Close and secure instrument panel.
c.
Testing. (VOLTS DC Meter)
(1) Release instrument panel by turning fastener, open instrument panel slowly.
(2) Remove gauge protective cover.
(3) Set multimeter for DC volts and connect to VOLTS DC meter terminals.
(4) Start and operate generator set at rated voltage (multimeter indication).
(5) Shut down generator set.
(6) Replace VOLTS DC meter if multimeter indicates DC voltage within rated range
(26.6-32.2 VDC) and meter does not.
(7) Install gauge protective cover.
(8) Close and secure instrument panel.
d.
Removal.
(1) Shut down generator set.
(2) Release instrument panel by turning fastener, open instrument panel slowly.
(3) Remove gauge protective cover. Then tag and disconnect VOLTS meter (Figure
4-24) electrical leads.
(4) Release instrument cover by turning fastener, open instrument cover.
4-74