ARMY TM 9-6115-673-13&P
AIR FORCE TO 35C2-3-512-1
a. The generator set is normally received either from the manufacturer or long term storage with
the fuel system drained, however, the crankcase will be filled with oil.
b. In order to put the generator set into service, perform the following procedure:
CAUTION
When checking the diesel engine lube oil level, the generator set must
be level. If it is tilted, an incorrect oil level may be indicated. Insert
dipstick into the oil pan. Do not screw in the dipstick. Overfilling can
cause overheating, increased oil pressure, and severe damage.
(1) Check oil level indicated on dipstick, see Figure 4-1. The proper viscosity of oil should be
used for the following conditions: (Refer to Items 13 and 14, Appendix E.)
-40 to 0F ...................................................................................... MIL-PRF-46167
(-40 to -18C)
OW30
0 to 120F ....................................................................................... MIL-PRF-2104
(-18 to 49C)
15W40