ARMY TM 9-6115-672-14
AIR FORCE TO 35C2-3-444-32
MARINE CORPS TM 09244A/09245A-14
4-126
(5)
Set multimeter for ohms, and measure resistance across resistor (10). Multimeter indication should
be between 1235 and 1365 ohms.
(6)
If any indications are other than above, replace resistor.
(7)
Install R1 and remove tags.
(8)
Install DCS control box top panel, paragraph 4.7.2.
(9)
Connect negative battery cable to battery, and close BATTERY ACCESS door.
c. Replacement.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open BATTERY ACCESS door (Figure 1-2), and disconnect negative battery cable.
(3)
Remove DCS control box top panel, paragraph 4.7.2.
(4)
Tag and desolder electrical leads from resistor (10, Figure 4-16)
(5)
Remove resistor (10) from auxiliary control bracket (18).
(6)
Install resistor (10) to auxiliary control bracket (18).
(7)
Solder electrical leads to resistor (10). Remove tags.
(8)
Install DCS control box top panel, paragraph 4.7.2.
(9)
Connect negative battery cable to battery, and close BATTERY ACCESS door.
4.8.31 Resistor R2.
a. Inspection.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Remove DCS control box top panel, paragraph 4.7.2.
(3)
Inspect resistor (13, Figure 4-16) for cracks, breaks, corrosion, bent terminals, and other damage.
(4)
Install DCS control box top panel, paragraph 4.7.2.
b. Testing.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open BATTERY ACCESS door (Figure 1-2), and disconnect negative battery cable.
(3)
Remove DCS control box top panel, paragraph 4.7.2.
(4)
Set multimeter for ohms, and measure resistance across resistor (13, Figure 4-16). Multimeter
indication should be between 310 and 350 ohms.