ARMY TM 9-6115-671-14
AIR FORCE TO 35C2-3-446-32
MARINE CORPS TM 09249A/09246A-14
4-184
(6)
Connect negative battery cable to battery and close battery access door.
(7)
Close output box access door.
b. Removal.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open BATTERY ACCESS door (Figure 1-2), and disconnect negative battery cable.
(3)
Open output box access door (Figure 1-2).
(4)
Remove locknuts (1, Figure 4-28), washers (2), and protective cover (3) from standoffs (4).
(5)
Remove locknuts (5) and moveable terminal board (6) from terminal studs (7).
c. Installation.
(1)
Install moveable terminal board (6, Figure 4-28) and locknuts (5) on terminal studs (7).
(2)
Install protective cover (3), washers (2), and locknuts (1) on standoffs (4).
(3)
Close output box access door.
(4)
Connect negative battery cable to battery, and close BATTERY ACCESS door.
4.12.2 Output Box Wiring Harness.
a. Inspection.
(1)
Shut down generator set, paragraph 2.11.2.
(2) Open output box access door (Figure 1-2).
(3)
Inspect wiring harness (8, Figure 4-28) for burned, bent, corroded, and broken terminals.
(4)
Inspect connectors for cracks, corrosion, stripped threads, bent or broken pins, and obvious damage.
(5)
Inspect wire insulation for burns, deterioration, and chafing.
(6)
Close output box access door.