ARMY TM 9-6115-671-14
AIR FORCE TO 35C2-3-446-32
MARINE CORPS TM 09249A/09246A-14
4-187
(5)
Set multimeter for ohms, and check for continuity between secondary terminals A1 and A2, B1 and
B2, and C1 and C2.
(6)
If continuity is not present, current transformer is defective. Notify next higher level of
maintenance.
(7)
If continuity is present, connect electrical leads to secondary terminals A1, A2, B1, B2, C1, and C2.
Remove tags.
(8)
Close output box access door.
(9)
Connect negative battery cable to battery, and close BATTERY ACCESS door.
4.12.4 Droop Current Transformer CT5.
a. Inspection.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open output box access door (Figure 1-2).
(3)
Inspect droop current transformer (10, Figure 4-28) for security, cracked housing, broken wire
terminals, and loose or missing hardware. If testing or replacement is required, notify next higher
level of maintenance.
(4)
Close output box access door.
4.12.5 Power Potential Transformer T1.
a. Inspection.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open output box access door (Figure 1-2).
(3)
Inspect potential power transformer (11, Figure 4-28) for security, cracked housing, broken wire
terminals, and loose or missing hardware. If testing or replacement is required, notify next higher
level of maintenance.
(4)
Close output box access door.