TM 9-6115-670-14&P
5-67
5.24. GENERATOR, 10 kW, 60 Hz.
This task covers: Replace
INITIAL SETUP
Tools
General Mechanic's Tool Kit
(Item 1, Appendix B)
Shop Equipment, Electrical Repair,
Semitrailer Mounted
(Item 3, Appendix B)
DS Shop Equipment
(Item 52, Appendix B)
Equipment Conditions
MASTER ON-OFF switch on APU control unit set
to OFF.
Governor control assembly disconnected (para
4.48.).
Wiring harness, Engine P1 disconnected (para
5.27.).
Materials/Parts
Generator Assembly
Air filter removed (para 4.45.).
REPLACE
a. Remove four screws (JTACS), or slotted hex-head bolts (SICPS and WIN-T), flat and lock
washers (4, Figure 5-18), and generator housing top cover (5).
b. Remove two screws, wing nuts and lock washers (9a) (JTACS), or four slotted hex-head bolts
(SICPS and WIN-T), flat and lock washers (9), and generator housing side cover (8) (muffler
side).
c. Remove four screws (JTACS), or four slotted hex-head screws (SICPS and WIN-T), flat and
lock washers (5, Figure 5-12), generator housing side cover (4) (fuel pump side).
d. Refer to FO-1 (SICPS, WIN-T) or FO-7 (JTACS). Tag and remove electrical leads F1 and F2
from relay board inside regulator box.
e. Refer to FO-1 (SICPS, WIN-T) or FO-7 (JTACS). Tag and remove ground wire U2L0 inside the
generator housing behind the electrical output terminal board.
f. Refer to FO-1 (SICPS, WIN-T) or FO-7 (JTACS). Tag and remove electrical leads U1T1,
U5T3, and U6T4 from terminals 1, 3 and 5 on the main contactor.
WARNING
Ensure that APU DC power supply is disconnected.
Failure to observe this warning could result in severe
injury of DEATH to personnel.
Ensure that the APU is turned off and completely de-
energized before opening generator housing.
Failure to observe this warning could result in
severe injury of DEATH to personnel.