TM 9-6116-669-13&P
a.
Check condition of the pallet frame. There must be no visible damage to the frame. Check that
all mounted parts in figure 4-27 are present and firmly attached.
b.
Check that the three grounding cables (4 to 7) are firmly attached, and that braiding is
undamaged.
c.
Check that the eight bolt fasteners (2) for the Generator Set 150 kW are in good condition and
move easily.
d.
Check operation of hinged fastener (28) and good condition of parts (12 to 17).
e. Check that lifting lugs (1) are in good condition.
f.
Check that rubber plates (27) are firmly attached. The plates are glued in position.
g. Check that mounting mechanism for fire extinguishers (18, 19) are in proper condition and
operate easily.
h. Check that parts (21 to 26) of ground rod box are in good condition.
NOTE
Check fire extinguishers at every inspection interval according
to labels.
4 - 6 0