ARMY TM 9-6115-644-24
AIR FORCE TO 35C2-3-446-12
MARINE CORPS TM 09249A/09246A-24/2
c.
Install control box) top panel, paragraph 2-15-4.
d. Connect negative battery cable. Close battery access door.
2-65 LOAD MEASURING UNIT.
2-65-1
a.
b.
2-65-2
a.
b.
c.
d.
e.
f.
2-65-3
a.
b.
c.
d.
e.
Inspection.
Shut down generator set.
Inspect load measuring unit for damaged case, cracked or broken terminal lugs, and loose or missing hardware.
Removal.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box top panel, paragraph 2-15-1.
Release control panel by turning two fasteners and lower control panel slowly.
Tag and disconnect load measuring unit (69, FIGURE 2-14) electrical leads.
Remove screws (68) and load measuring unit (69).
Installation.
Install load measuring unit (69, FIGURE 2-14) with screws (68).
Connect all electrical leads and remove tags.
Install control box top panel, paragraph 2-15-4.
Raise and secure control panel.
Connect negative battery cable. Close battery access door.
2-66
RESISTOR-DIODE ASSEMBLY.
2-66-1
a.
b.
2-66-2
a.
b.
c.
d.
e.
f.
2-102
Inspection.
Shut down generator set.
Inspect resistor diode assembly for cracks, breaks, corrosion, bent terminals, and other damage.
Testing.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Release control panel by turning two fasteners and lower control panel slowly.
Set multimeter for ohms and measure resistance across resistors R10, R11, and R12. Multimeter indication
should be between 7.125 and 7.875 ohms for each resistor.
Using multimeter, measure resistance across resistor R14. Multimeter indication should be between 61.75 and
68.25 ohms for MEP-805A generator set, and between 38 and 42 ohms for MEP-815A generator set.
Using multimeter, measure resistance across resistor R15. Multimeter indication should be between 1235 and
1365 ohms.