d. Connect negative battery cable. Close battery access door.
2-62 CONTROL BOX HARNESS.
2-62-1
a.
b.
2-62-2
a.
b.
c.
d.
e.
2-62-3
a.
b.
Inspection.
Shut down generator set.
Inspect control box harness (57, FIGURE 2-14) wiring for breaks, damaged insulation, and loose or damaged
terminals.
Testing.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box top panel, paragraph 2-15-1.
Set multimeter for ohms, and using Wiring Diagram FO-2 as a guide, check wires for continuity.
If no repair is needed, install control box top panel, paragraph 2-15-4, connect negative battery cable, and close
battery access door.
Repair.
Replace individual wires, damaged terminal ends, clamps, and tie wraps.
Ensure proper connection of wires not indicating continuity.
2-63 DIAGNOSTIC CONNECTOR.
2-63-1
a.
b.
c.
d.
e.
f.
g.
2-63-2
a.
2-98
NOTE
The diagnostic connector can be used as an aid in troubleshooting. Refer to FIGURE
2-17 and TABLE 2-9.
NOTE
Diagnostic connector is a component of the control box harness assembly, but can be
removed and installed separately as follows.
Inspection.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Inspect diagnostic connector for cracks, breaks, corrosion, bent terminals, bums, or other indications of dam-
age.
Inspect cap for cracks, corrosion or broken chain.
Inspect gasket for tears and deterioration.
Replace any defective part.
If no repair is needed, connect negative battery cable and dose battery access door.
Removal.
Shut down generator set.