Table 2-1. Operator Preventive Maintenance Checks and Services for MEP 831A / 832A (continued)
Item
No.
Interval
Location:
Item to
Check/
Service
Procedure
Not Fully Mission
Capable If:
4
Before
Convenience
receptacle
(60Hz only)
Inspect receptacle for damage. Check for
signs of electrical short or corrosion.
Receptacle damaged,
shorted, or corroded.
5
Before
NATO slave
receptacle
Inspect receptacle for damage. Check for
signs of electrical short or corrosion.
Receptacle damaged,
shorted, or corroded.
6
Before
Output panel
a. Inspect output panel door for security.
Check that locking latch operates properly.
WARNING:
Ensure generator set is properly grounded
prior to starting. Failure to properly ground
can result in serious injury or death through
electrocution.
b. Check load and ground terminals for
security of attachment. Inspect for
signs of electrical short or corrosion.
c. Check ground rod cable for proper
installation. Check for correct connection.
Terminals are loose,
disconnected, shorted,
damaged, or corroded.
Set is not grounded
properly.
2-13