TM5-6115-640-14&P
c.
Installation.
(1)
Route power cable through power cable brackets.
(2)
Feed cable through cable clamping nut (19) and through hole into switch box (5).
(3)
Tighten clamping nut (19) on outside of switch box (5) to prevent cable from moving.
(4)
Slide washer (12) and terminal of white wire (11) on load terminal (13) LO and secure with lockwasher (10) and
nut (9).
(5)
Slide terminal of green wiring (17), and other green wiring, if necessary, on E1 (18) and secure with flat washer
(16), lockwasher (15), and nut (14).
NOTE
Observe identification tags when installing wires.
(6)
Position each of three wires (7) (black, red and blue) against underside of its respective switch terminal (8).
Insert screw (6) through wire terminal and tighten on threaded switch terminal. Where an indicator light wire is
also mounted to the switch terminal, the indicator light wire shall be positioned against the underside of the
switch terminal and the power cable wire shall be positioned against the indicator light wire.
(7)
Position cover (4) on switch box (5) and secure with 16 screws (1), lockwashers (2) and flat washers (3).
(8)
Connect power cable to load terminals on generator set. (Refer to TM5-6115-615-12).
4-41