ARMY TM 5-6115-629-14&P
AIR FORCE TO-35C2-3-488-1
NOTE
Because both a 4-wire or 5-wire switch box may be supplied with the AN/MJQ-
12A, the NSN on switch box identification plate will be either NSN 6110-01-038-3732
(4-wire) or Part Number 13226E6296, FSCM 97403 (5-wire).
(6) Instruction P/ate.
(a) Location. This plate is located on the outside of switch box access door.
(b) Content.
OPERATING INSTRUCTIONS
A. PRIOR TO OPERATION, READ INSTRUCTION MANUAL FURNISHED WITH THE POWER
UNIT (GENERATOR SET), INCLUDING APPLICABLE REVISION SHEETS.
B. INSURE GENERATOR CIRCUIT BREAKERS AND SWITCH BOX SWITCHES ARE IN THE
OFF POSITION.
C. TO OPERATE ONE UNIT, THIS PROCEDURE SHOULD BE FOLLOWED:
1. CONNECT ALL NECESSARY CABLES TO THE GENERATOR AND SWITCH BOX
ASSEMBLY.
2. BRING GENERATOR UP TO RATED SPEED, VOLTAGE AND FREQUENCY.
3. CLOSE GENERATOR CIRCUIT BREAKER.
4. MOVE SWITCH BOX SWITCH, CORRESPONDING TO GENERATOR USED, TO
ON POSITION.
5. POWER IS NOW SUPPLIED TO SWITCH BOX OUTPUT TERMINALS.
D. TO OPERATE TWO UNITS IN PARALLEL, THIS PROCEDURE SHOULD BE FOLLOWED:
1.
2.
3.
4.
5.
6.
CONNECT ALL NECESSARY CABLES TO GENERATORS AND SWITCH BOX
ASSEMBLY.
BRING FIRST GENERATOR INTO OPERATION ACCORDING TO THE PROCEDURE
OUTLINED IN SECTIONS B AND C.
BRING SECOND GENERATOR UP TO RATED SPEED, VOLTAGE AND
FREQUENCY.
MOVE SWITCH BOX SWITCH, CORRESPONDING TO THE SECOND GENERATOR,
TO ON POSITION.
CLOSE CIRCUIT BREAKER ON SECOND GENERATOR.
THE PARALLELING OPERATING SHOULD BE COMPLETE.
1-6