TM 9-6150-226-13
Table 4-4.
DISE AND PDISE FEEDER/DISTRIBUTION CENTER CONTINUITY CHECKS (cont)
NOTE
Refer to paragraph 4-14 for DISE and paragraph 4-17 for
PDISE and expose phase bus bars as necessary.
All checks
are made with circuit breakers closed.
X indicates continuity.
O indicates no continuity.
J6-A
J6-B
J6-C
J7-A
J7-B
J7-C
J8-A
J8-B
J8-C
d.
M60 and M60 A/P Distribution Center. (cont)
Phase A (L1)
Neutral (LO)
Ground (G)
x
0
0
0
x
0
0
0
x
x
0
0
0
x
0
0
0
x
x
0
0
0
x
0
0
0
x
Table 4-5.
DUPLEX RECEPTACLE CONTINUITY CHECKS
X indicates continuity.
O indicates no continuity.
(See Fig. 4-9.)
Duplex Receptacle
Phase Line
Neutral Line
Ground Line
Input
(Black Wire)
(White Wire)
(Green Wire)
Connector
(Short Slot)
(Long T-slot)
(Ground Slot)
J1-A
x
0
0
J1-B
0
x
0
J1-C
0
0
x
4-19