TM 9-6150-226-13
Table 4-8.
DISE AND POISE CABLE CONTINUITY CHECKS
WARNING
High voltage is present in this system.
DISE and PDISE
supports equipment using 120/208 V ac.
Do not rely on the
color of the wire insulation for phase color coding.
The
insulation on the wires inside the cable jacket may vary
depending on supplier.
Wires will be color coded to
designate the phases.
Perform a continuity test to verify
phase designation is in accordance with identified color.
X indicates continuity
O indicates no continuity
a.
200- and 100-Amp, 8 Wire Service/Feeder Cables.
P1-A
P1-B
P1-C
P1-N
P1-G1
P1-G2
P1-G3
P1-G4
P2-A
x
o
0
0
0
0
0
0
P2-B
o
x
o
0
0
0
0
0
P2-C
o
0
x
o
0
0
0
0
P2-N
o
0
0
x
o
0
0
0
P2-G1
o
0
0
0
x
x
x
x
P2-G2
o
0
0
0
x
x
x
x
P2-G3
o
0
0
0
x
x
x
x
P2-G4
o
0
0
0
x
x
x
x
b.
40/60-Amp, 5-Wire Service/Feeder Cables.
Pi-A
Pi-B
Pi-C
Pi-N
Pi-G
P2-A
x
0
0
0
0
P2-B
0
x
0
0
0
P2-C
0
0
0
0
P2-N
0
0
x
0
P2-G
0
0
0
0
x
4-21