TM 9-6150-226-13
Table 4-4.
DISE AND PDISE FEEDER/DISTRIBUTION CENTER CONTINUITY CHECKS (cont)
NOTE
Refer to paragraph 4-14 for DISE and paragraph 4-17 for
PDISE and expose phase bus bars as necessary.
All checks
are made with circuit breakers closed.
X indicates continuity.
O indicates no continuity.
b.
M100 Feeder Center (see Fig.
4-2) and M1OO A/P Feeder Center (see
Fig. 4-6).
J1-A
J1-B
J1-C
J1-N
J1-G1
J1-G2
J1-G3
J1-G4
J2-A
J2-B
J2-C
J2-N
J2-G1
J2-G2
J2-G3
J2-G4
J3-A
J3-B
J3-C
J3-N
J3-G
J4-A
J4-B
J4-C
J4-N
J4-G
J5-A
J5-B
J5-C
J5-N
J5-G
Phase A (L1)
x
0
0
0
0
0
0
0
x
0
0
0
0
0
0
0
x
0
0
0
0
x
0
0
0
0
x
0
0
0
0
Phase B (L2)
0
x
0
0
0
0
0
0
0
x
0
0
0
0
0
0
0
x
0
0
0
0
x
0
0
0
0
x
0
0
0
Phase C (L3)
0
0
x
0
0
0
0
0
0
0
x
0
0
0
0
0
0
0
x
0
0
0
0
x
0
0
0
0
x
0
0
Neutral (LO) Ground (G)
0
0
0
0
0
0
x
0
0
x
0
x
0
x
0
x
0
0
0
0
0
0
x
0
0
x
0
x
0
x
0
x
0
0
0
0
0
0
x
0
0
x
0
0
0
0
0
0
x
0
0
x
0
0
0
0
0
0
x
0
0
x
4-15