TM 9-6115-730-24
0074
REMOVAL
1. Ensure generator set is fully stopped, ENGINE CONTROL switch is OFF/RESET, Battery Disconnect Switch is
OFF, and DEAD CRANK SWITCH is OFF before proceeding.
2. Open right front doors.
3. Tag and disconnect wiring from alternator. Note routing of alternator belts (Figure 1, Item 1).
4. Loosen nut (Figure 1, Item 2) and turn nut (Figure 1, Item 2) counterclockwise (CW) to relieve tension on
alternator belts (Figure 1, Item 1) and slip belts off alternator pulley (Figure 1, Item 4).
5. Tag and disconnect wiring from alternator (Figure 1, Item 5).
WARNING
Support alternator when removing attaching hardware or alternator may fall. Failure to comply
can cause injury to personnel and equipment damage.
6. While supporting alternator (Figure 1, Item 5), remove nut (Figure 1, Item 6), two washers (Figure 1, Item 7),
and bolt (Figure 1, Item 8).
7. Remove bolt (Figure 1, Item 9), washer (Figure 1, Item 10), and alternator (Figure 1, Item 5).
END OF TASK
INSTALLATION
WARNING
Support alternator when removing attaching hardware or alternator may fall. Failure to comply
can cause injury to personnel and equipment damage.
1. Install alternator (Figure 1, Item 5) and secure with washer (Figure 1, Item 10) and bolt (Figure 1, Item 9).
Tighten bolt.
2. Install bolt (Figure 1, Item 8), two washers (Figure 1, Item 7), and nut (Figure 1, Item 6). Tighten nut.
3. Position alternator belts (Figure 1, Item 1) onto alternator pulley (Figure 1, Item 4), check positioning of belt and
turn nut (Figure 1, Item 2) clockwise (CW) to increase tension on belts.
4. Connect wiring to alternator (Figure 1, Item 5).
5. Perform belt tension adjustment.
6. Install upper right and lower right fan guards (WP 0066).
0074-2