TM 9-6115-730-24
0042
LSM A4 LOAD GAIN ADJUSTMENT
NOTE
For this procedure the generator set must be running isochronously, not paralleled.
1. Start the generator set and run at full load.
2. Measure the load signal voltage at LSM A4-22 (+) and LSM A4-23 (-).
3. Adjust LSM A4 LOAD GAIN potentiometer for 6.0 Vdc 1.0 Vdc.
END OF TASK
END OF WORK PACKAGE
0042-14