TM 9-6115-730-24
UNIT (FIELD) LEVEL MAINTENANCE
TACTICAL QUIET GENERATOR 200 kW, 50/60 Hz MEP-809A/PU-809A
FRONT SECTION HOUSING ASSEMBLY MAINTENANCE
INITIAL SETUP:
Equipment Condition
Tools and Special Tools
Right battery access door assembly removed
Tool Kit, General Mechanic's (WP 0123, Item 1)
Left battery access door assembly removed
Materials/Parts
Left front door assembly (latch) removed
Right front door assembly (latch) removed
Personnel Required
Engine generator compartment ceiling removed
One
References
TM 9-6115-730-24P
Winterization heater assembly removed, if
WARNINGS
components. Remove all jewelry when working on generator set. Failure to comply can cause
injury or death to personnel by electrocution.
DO NOT wear loose clothing when performing checks, services and maintenance. Failure to
comply can cause injury or death to personnel.
High voltage is produced when this generator set is in operation. Make sure unit is completely shut
down and free of any power source before attempting any repair or maintenance on the unit.
Failure to comply can cause injury or death to personnel.
High voltage is produced when the generator set is in operation. Never attempt to start or
maintain the generator set unless it is properly grounded. Failure to comply can cause injury or
death to personnel.
REMOVAL
1.
Remove six screws (Figure 1, Sheet 1, Item 1), lockwashers (Figure 1, Sheet 1, Item 2), washers (Figure 1,
Sheet 1, Item 3), and nuts (Figure 1, Sheet 1, Item 4).
0034-1