TM 9-6115-729-24
UNIT (FIELD) LEVEL MAINTENANCE
TACTICAL QUIET GENERATOR 100 kW, 50/60 Hz MEP-807A/PU-807A
REAR ROOF SECTION HOUSING ASSEMBLY MAINTENANCE
INITIAL SETUP:
Tools and Special Tools
Personnel Required
Tool Kit, General Mechanic's (WP 0119, Item 1)
Two
Materials/Parts
References
TM 9-6115-729-24P
Equipment Condition
Front roof section housing assembly removed
WARNINGS
Metal jewelry will conduct electricity. All jewelry can become entangled in generator set
components. Remove all jewelry when working on generator set. Failure to comply can cause
injury or death to personnel by electrocution.
DO NOT wear loose clothing when performing checks, services and maintenance. Failure to
comply can cause injury or death to personnel.
High voltage is produced when this generator set is in operation. Make sure unit is completely shut
down and free of any power source before attempting any repair or maintenance on the unit.
Failure to comply can cause injury or death to personnel.
High voltage is produced when the generator set is in operation. Never attempt to start or
maintain the generator set unless it is properly grounded. Failure to comply can cause injury or
death to personnel.
WARNING
Top housing panels can get very hot. Allow panels to cool down before performing maintenance.
Failure to comply can result in severe burns to personnel.
REMOVAL
1. Remove 18 screws (Figure 1, Sheet 1, Item 1), lockwashers (Figure 1, Sheet 1, Item 2), and washers (Figure
1, Sheet 1, Item 3) from rear roof housing assembly (Figure 1, Sheet 1, Item 4).
2. Remove seven screws (Figure 1, Sheet 1, Item 5), lockwashers (Figure 1, Sheet 1, Item 6), and washers
(Figure 1, Sheet 1, Item 7).
0030-1