TM 9-6115-729-10
0010 00
TROUBLESHOOTING PROCEDURES Continued
CAUTION
The maximum power rating for the convenience receptacle is 15A. To prevent circuit breaker from
opening, the total current drawn should be limited to 15A only. Failure to limit the load to less than
15A may trip the circuit breaker and damage the generator set or load.
9. Convenience receptacle on
1. Check that load is no more than
If load is greater than 15A, reduce load.
15A.
panel has no power.
2. Turn off equipment powered by
all plugs from outlets.
3. Check GROUND FAULT
If tripped, reset thermal overload on
CIRCUIT INTERRUPTER (GFCI)
GROUND FAULT CIRCUIT
INTERRUPTER circuit breaker
4. Under GROUND FAULT
If TEST window is not red when TEST
CIRCUIT INTERRUPTER
is pressed, notify maintenance.
nameplate press TEST pushbutton
on GFCI circuit breaker.
5. Press RESET pushbutton on GFCI
If TEST window is not clear when
circuit breaker.
RESET is pressed, notify
maintenance.
6. Check load is no more than 15A and
If load is greater than 15A, reduce size
for possible ground fault.
of load. If no ground fault or
overload exists, plug equipment
back into convenience receptacle.
10. Winterization kit (issued to selected
1. On FUEL FIRED HEATER
If switch is OFF, set to ON.
units only) is not operating. Red
CONTROL panel, press CIRCUIT
DIAGNOSTIC light is on.
BREAKER and verify that switch is
set to ON and indicator is lit.
2. Push press to test press-to-test
If indicator does not light, notify
HEATER indicator light.
maintenance.
3. Verify red DIAGNOSTIC light is
Set CIRCUIT BREAKER switch to
on.
OFF and notify maintenance.
END OF TASK
0010 00-8