TM 9-6115-729-10
0010 00
TROUBLESHOOTING PROCEDURES Continued
Table 1. Operator Troubleshooting Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
7. Alarm module GENERATOR
3. Set Battery Disconnect Switch to
OVERLOAD amber indicator
OFF.
flashes. TQG disconnects from
load. Continued
4. Check load connected to TQG to
Repair cause of overload or notify
see if there was a problem there that
maintenance.
could cause TQG to overload.
5. Determine if load is too large for
Reduce load below output capacity of
generator set.
cannot be larger than TQG rating.)
6. Determine if load has been
Reduce load as necessary.
increased.
7. Set Battery Disconnect Switch to
ON.
8. Set DEAD CRANK SWITCH to
NORMAL.
9. Set ENGINE CONTROL switch to
STOP COOL/DOWN.
10. Press LAMP TEST on alarm
module to reset overload fault
detection circuit.
11. Start and operate TQG
1. Monitor TQG for further problems.
2. If there is no identifiable problem
with the load and alarm recurs,
notify maintenance.
8. Alarm module LOW FUEL LEVEL
1. On EMCP, verify low fuel level on
1. If required, service and fill fuel tank
red indicator glows steady. TQG
fuel gauge.
engine shuts down.
2. Check that auxiliary fuel source is
If needed, connect auxiliary fuel hose
in use.
3. On EMCP, verify AUX FUEL
Set AUX FUEL pump switch to ON.
pump switch is set to ON.
4. Verify that external (auxiliary) fuel
If external fuel is present at source,
source is present and that there is
notify maintenance to troubleshoot
fuel in external fuel source
auxiliary fuel pump.
container.
0010 00-7