TM 9-6115-729-10
100 kW TACTICAL QUIET GENERATOR SET
0010 00
TROUBLESHOOTING PROCEDURES Continued
Table 1. Operator Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
5. GSC LOW COOLANT LEVEL red
1. Set ENGINE CONTROL switch to
indicator flashes.
COOL DOWN/STOP.
2. Set DEAD CRANK SWITCH to
OFF.
3. Set Battery Disconnect Switch to
OFF.
4. Allow engine to cool.
5. Check coolant level in coolant
1. If coolant level is low, refill coolant
overflow bottle with correct mixture
of water and coolant per
2. Monitor coolant level and refill as
required.
6. Visually inspect radiator and
Remove obstructions and debris from
coolant system for damage, leaks,
fan guards and shroud area, tighten
loose clamps, fan guards, fan, and
clamps. If radiator is obstructed
shrouds or obstructions per
and coolant system damaged or you
cannot tighten clamps, notify
maintenance.
_________
WARNING
Metal jewelry can conduct electricity and become entangled in generator set components. Remove
all metal jewelry when working on generator set. Failure to comply can cause injury or death to
personnel.
High voltage is produced when this generator set is in operation. Make sure unit is completely shut
down and free of any power source before attempting any repair or maintenance on the unit. Failure
to comply can cause injury or death to personnel.
DC voltages are present at generator set electrical components even with generator set shut down.
Avoid shorting any positive with ground/negative. Failure to comply can cause injury to personnel
and damage to equipment.
6. Alarm module OVERCURRENT
1.
Set ENGINE CONTROL switch to
amber indicator flashes.
OFF/RESET.
TQG disconnects from
2. Set DEAD CRANK SWITCH to
load.
OFF.
3.
Set Battery Disconnect Switch to
OFF.
0010 00-5