ARMY TM 9-6115-673-13&P
AIR FORCE TO 35C2-3-512-1
(14) Start diesel engine and attempt to close ON-OFF load circuit breaker. The circuit breaker
should open instantaneously.
(15) Shutdown engine and remove cable from output load terminals.
(16) Replace generator control unit if any of above readings are not as stated.
(17) Close and secure instrument panel.
d. Removal.
(1) Shut down generator set.
(2) Release instrument panel by turning fastener, open instrument panel slowly.
(4) Tag and disconnect electrical leads for generator control unit (Figure 5-1) from terminals on
terminal board TB1.
e. Installation.