ARMY TM 9-6115-673-13&P
AIR FORCE TO 35C2-3-512-1
(9) Close and secure instrument panel.
d.
Installation.
(1) Install instrument shunt (Figure 4-28) in control panel and secure with screws,
(2) Connect wires to instrument shunt terminals as tagged. Remove tags.
(3) Close and secure instrument panel.
CAPACITOR. (MEP-501A)
a.
Inspection.
(2) Release instrument panel by turning fastener, open instrument panel slowly.
(3) Inspect capacitor for security, overheating, and other damage.
(4) Close and secure instrument panel.
b.
Removal.
(2) Release instrument panel by turning fastener, open instrument panel slowly.
(3) Cut tie down strap securing capacitor (Figure 4-29) to mount.
(4) Tag and disconnect capacitor at terminal board and at load terminal (-). Remove
capacitor from control panel.
c.
Testing.
(2) Release instrument panel by turning fastener, open instrument panel slowly.
(3) Disconnect wire C1 (-)↔(-) at load terminal (-) and wire C1 (+)↔CB1-P1 (Line) at
circuit breaker CB1.
and note resistance.
(5) Resistance should be high in one direction and low in the other. If resistance is
high or low in both directions, replace capacitor.