ARMY TM 9-6115-673-13&P
AIR FORCE TO 35C2-3-512-1
GROUND ROD
GROUND
STUD
GROUND CABLE
Figure 2-2. Grounding Connections (Typical Installation)
b. Installation of Load Cables.
WARNING
Never attempt to connect or disconnect load cables while the
generator set is running. Failure to observe this warning could
result in severe personal injury or death by electrocution.
(1) If operating, shut down generator set and open load terminal board cover.
(2) Using suitable wrenches, hold terminal body hex with one wrench and loosen terminal
nuts (Figure 2-3) on terminals "L" and "N" (MEP-531A) or "+" and "-" (MEP-501A).
(3) Insert ends of load cables through load cable exit. Then insert ends of cables into
slots of load terminal studs.
(4) Hold terminal body hex with one wrench and tighten load terminal nuts and lock
retaining clips. Then close and secure load terminal board cover.