1.22.4.1. The generator set is brought on line by placing the ON-OFF load circuit breaker (CB1) in the ON position.
The circuit breaker is a single pole, shunt trip switch with momentary contacts that return it to the neutral, or center
position when the toggle switch is released. Load terminals L and N are energized by this momentary contact to bring
the generator set on line.
DYNAMO
(G1)
DIESEL
RESISTOR
(G2)
ENGINE
(R3)
F1
REG.
VOLTAGE
VOLT.
REGULATOR
M2
M1
ADJ.
(A1)
(R2)
VOLTAGE REGULATION
M1 - % LOAD METER
M2 - VOLTS METER
Figure 1-9. Generator Voltage Regulation System (MEP-501A)
1.22.4.2. Placing the ON-OFF load circuit breaker (CB1) momentarily in the OFF position opens the line to the load
terminals and takes the generator set off line.
1.22.4.3. There is a transient suppression diode assembly consisting of two diodes (CR2 and CR3) at the load
terminals (+ and -) on MEP-501A. These diodes protect the load circuit from potential damage resulting from cross
connecting the + and - output terminals on the alternator (G2). The diodes prevent damage by only allowing the
current to flow in the generator circuit in one direction.