ARMY TM 9-6115-673-13&P
AIR FORCE TO 35C2-3-512-1
1.21.4.1. The generator set is brought on line by placing the ON-OFF load circuit breaker (CB1) in the ON position.
The circuit breaker is a single pole, shunt trip switch with momentary contacts that return it to the neutral, or center
position when the toggle switch is released. An EMI filter (MEP-531A) or load terminals L and N (Mechron 120 VAC
set) are energized by this momentary contact to bring the generator set on line. The GFCI convenience receptacle (J3)
is also energized by ON-OFF load circuit breaker (CB1). The GFCI convenience receptacle (J3) features a ground
fault interrupter which protects the generator set components from inductive current in the ground circuit originating
from the load connected to the GFCI receptacle (J3).
1.21.4.2. Placing the ON-OFF load circuit breaker (CB1) momentarily in the OFF position opens the line to the load
terminals and takes the generator set off line. The ON-OFF load circuit breaker features a diode (CR2) which protects
the generator set components by allowing current to flow in only one direction.
LEGEND
AC
Line
Neutral
(G2)
CIRCUIT
BREAKER
(CR2)
(CB1)
CONVENIENCE
RECEPTACLE
(J3)
L
N
EMI
FILTER*
(FLI)
*MECHRON 120VAC SET HAS
LOAD
LOAD TERMINALS (L AND N)
DISTRIBUTION
AND A LOAD TERMINAL BOARD
(EXTERNAL)