ARMY TM 9-6115-672-14
AIR FORCE TO 35C2-3-444-32
MARINE CORPS TM 09244A/09245A-14
5-41
5.9
MAINTENANCE OF ENGINE ACCESSORIES.
__________
WARNING
When disconnecting or removing batteries, disconnect the negative lead
that connects directly to the grounding stud first. Disconnect the negative
end of the interconnection cable next. When installing batteries, reverse the
connection sequence. Failure to comply can cause serious personal injury.
5.9.1
Electric Actuator A6.
a. Inspection.
Inspect electric actuator (11, Figure 5-7) for corrosion, dents, missing hardware, and obvious damage.
b. Testing.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open BATTERY ACCESS door (Figure 1-2), and disconnect negative battery cable.
(3)
Disconnect output box wiring harness from electrical connector (1, Figure 5-7).
(4)
Set multimeter for ohms. Test continuity at contacts within electrical connector (1). Multimeter
should indicate continuity.
(5)
If multimeter reading is other than above, replace electric actuator (11, Figure 5-8).
(6)
Connect electrical connector (1) to output box wiring harness.
(7)
Connect negative battery cable to battery, and close BATTERY ACCESS door.