ARMY TM 9-6115-672-14
AIR FORCE TO 35C2-3-444-32
MARINE CORPS TM 09244A/09245A-14
4-161
(3)
Install fan guards, paragraph 4.10.3.
(4)
Install radiator cap (1) on filler neck (2).
(5)
Connect negative battery cable to battery, and close BATTERY ACCESS door.
(6)
Start generator set, paragraph 2.11.1. Allow unit to reach operating temperature, and check for
leaks.
(7)
Add coolant/antifreeze to overflow bottle as required.
(8)
Close engine compartment access doors.
(9)
Shut down generator set.
4.10.6 Coolant Overflow and Drain Hoses.
a. Removal.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open BATTERY ACCESS door (Figure 1-2), and disconnect negative battery cable.
(3)
Open engine compartment access doors (Figures 1-2 and 1-3).
(4)
Open coolant drain valve (33, Figure 4-22), and drain coolant/antifreeze into suitable container.
(5)
Locate overflow or drain hose to be removed as shown in Figure 4-22.
(6)
Disconnect hose at both ends, and remove from generator set.
b. Inspection.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open engine compartment access doors (Figures 1-2 and 1-3).
(3)
Inspect hoses (15, Figure 4-22) for cracks, holes, and rotting.
(4)
Close engine compartment access doors.
c. Installation.
(1)
Install overflow or drain hose (15, Figure 4-22) in generator set as removed.
(2)
Close coolant drain valve (33), and add coolant/antifreeze to proper level at the filler neck (2).
(3)
Connect negative battery cable to battery, and close BATTERY ACCESS door.
(4)
Start generator set, paragraph 2.11.1. Allow unit to reach operating temperature, and check for
leaks.
(5)
Add coolant/antifreeze to overflow bottle as required.