ARMY TM 9-6115-671-14
AIR FORCE TO 35C2-3-446-32
MARINE CORPS TM 09249A/09246A-14
4-208
4.16
CIM CONFIGURATION SWITCH
An eight position DIP Switch illustrated below is located beneath a protective plastic cover on the front of
the Computer Interface Module. This switch defines the configuration of the generator set for the
Computer Interface Module. The generator set configuration is defined in two ways: Output power
(KW) rating, and Frequency rating. This switch must be set to a specific configuration
corresponding to the table below prior to the modules use in the generator set. Unless this switch is
properly configured, the generator set can experience a malfunction.
Configuration Switches Description:
There are eight rocker-type switches in one switch assembly, which is accessible from the front of the module. Each switch is
numbered left to right when viewing the module from the front. Each may be placed in either a up (on) or down (off) position,
which correspond to a logical 1 or 0 configuration.
SWITCH NUMBER
WHAT CONFIGURATION IS CONTROLLED BY THESE SWITCHES
1- 4
Power rating (30, 60 KW)
5
Frequency (50/60 or 400 Hz)
6-8
Not assigned.
The switch positions applicable to the 30 KW TQG sets are as follows:
Input/Output Module, Model TCM100:
SWITCH
1
2
3
4
5
6
7
8
GEN SET TYPE
Setting
off
off
off
off
off
off
off
off
30 KW, 50/60 Hz MEP-805B
Input/Output Module, Model TCM400:
SWITCH
1
2
3
4
5
6
7
8
GEN SET TYPE
Setting
off
off
off
off
on
off
off
off
30 KW, 400 Hz MEP-815B