b. Testing.
(1)
Start generator set, paragraph 2.11.1. Operate generator set at rated voltage and frequency.
(2)
Set multimeter for AC volts, press TEST button on GROUND FAULT CIRCUIT INTERRUPTER
(32, Figure 4-13), and check for zero voltage at the CONVENIENCE RECEPTACLE (23, Figure 4-
14) by inserting multimeter leads into one of the outlets.
(3)
Press RESET button on GROUND FAULT CIRCUIT INTERRUPTER (32, Figure 4-13), and use
multimeter to check for 120 VAC at the CONVENIENCE RECEPTACLE (23, Figure 4-14).
(4)
If indications are other than the above, replace GROUND FAULT CIRCUIT INTERRUPTER (32,
Figure 4-13).
c. Replacement.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open BATTERY ACCESS door (Figure 1-2), and disconnect negative battery cable .
(3)
Remove DCS control box top panel, paragraph 4.7.2.
(4)
Tag and disconnect GROUND FAULT CIRCUIT INTERRUPTER (32, Figure 4-13) electrical
leads from TB5 and CONVENIENCE RECEPTACLE (23, Figure 4-14).
(5)
Remove nuts (30, Figure 4-13), screws (31), and GROUND FAULT CIRCUIT INTERRUPTER
(32) from DCS control panel.
(6)
Install GROUND FAULT CIRCUIT INTERRUPTER (32), screws (31), and nuts (30) on DCS
control panel.
(7)
Connect GROUND FAULT CIRCUIT INTERRUPTER (32) electrical leads to CONVENIENCE
RECEPTACLE (23, Figure 4-14) and TB5. Refer to Schematic FO-1. Remove tags.
(8)
Install DCS control box top panel, paragraph 4.7.2.
(9)
Connect negative battery cable to battery, and close BATTERY ACCESS door.