ARMY TM 9-6115-671-14
AIR FORCE TO 35C2-3-446-32
MARINE CORPS TM 09249A/09246A-14
4-98
(8)
If indications are not as above, replace EMERGENCY STOP switch.
(9)
Connect electrical leads to EMERGENCY STOP switch (29), and remove tags.
(10) Raise and secure DCS control panel with two fasteners.
(11) Connect negative battery cable to battery, and close BATTERY ACCESS door.
c. Replacement.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open BATTERY ACCESS door (Figure 1-2), and disconnect negative battery cable.
(3)
Release DCS control panel by turning two fasteners, and lower DCS control panel slowly.
(4)
Tag and disconnect electrical leads from EMERGENCY STOP switch (29, Figure 4-13).
(5)
Unscrew and remove knob (27) and collar (28) from EMERGENCY STOP switch (29), and remove
switch from DCS control panel.
(6)
Position EMERGENCY STOP switch (29) on DCS control panel and secure with collar (28) and
knob (27).
(7)
Connect electrical leads to EMERGENCY STOP switch (29), and remove tags.
(8)
Raise and secure DCS control panel with two fasteners.
(9)
Connect negative battery cable to battery, and close BATTERY ACCESS door.
4.8.15 GROUND FAULT CIRCUIT INTERRUPTER CB3.
a. Inspection.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Release DCS control panel by turning two fasteners, and lower DCS control panel slowly.
(3)
Inspect GROUND FAULT CIRCUIT INTERRUPTER (32, Figure 4-13) for cracks, corrosion,
frayed wires, and other damage.
(4)
Raise and secure DCS control panel with two fasteners.