TM 9-6115-669-13&P
Table 2-9 Electric Power Plant III, Operator Preventive Maintenance Checks and Services
(PMCS).
Item
Number
1
Before
Pallet Frame
2
Before
support Arms, walk-
ways, Chains, Stan-
chions and Comer Pan-
els
3
Before
PDU Control Cabinet
4
Before
Power Cable Reels
5
Before
Control Cable Reel
6
Before
Fire Extinguisher
7
Before
Grounding Rod and
Check ground connection at-
Ground Cable (Rod to
tachment of grounding cables.
PDU)
Loose or missing hardware.
8
Before
Ground Cables (Genera-
Check ground connection be-
Ground cable is loose,
tor Set to Pallet Frame
tween Generator Set and Pallet
missing or broken.
and Pallet Frame to
Frame and Pallet frame to
Loose or missing hard-
Truck)
truck.
ware.
Interval
Location
Item to Check/Service
Procedure
Capable if:
Pallet must be secure to truck
chassis.
Check: Support Arms, Walk-
ways, Chains, Stanchions must
be secure.
Check:Cabinet is in place and
secure. Electrical connections
are accomplished. Shock ab-
sorbers are secure and all con-
trols and indicators are in place
and secure.
Check for loose or missing hard-
ware and operation of swing
mounts ratchet and release
mechanisms.
Check for operation of reel,
ratchet and release mechanism.
Check for presence of two extin-
guishers and pins and seals.
Not Fully Mission
Pallet frame is not se-
cure to truck chassis.
Loose broken or missing
hardware.
Support Arms and
Walkways are not se-
cure, comers are miss-
ing. Chains and Stan-
chions are not in place,
loose broken or missing
hardware.
Cabinet is not secure,
electrical connections
are not connected or se-
cure. Shock absorbers
are not secure, indica-
tors and controls are not
present or secure. Loose
or missing hardware,
knobs or switches.
Swing mounts will not
swing. Reels will not al-
low cable to be un-
reeled. Ratchet releases
will not operate or loose
or missing hardware.
Reel will not allow cable
to be unreeled. Release
mechanism will not op-
erate. Loose or missing
hardware.
Fire extinguishers are
missing or pins removed
or seals broken.
Ground rod is missing,
not attached to ground
cable, ground cable is
not attached to PDU.
2 - 2 9