Table 2-1 Control Cabinet Assembly, Description of Controls and Indicators.
Item
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Description
AMPS L1(ØA) meter 0 - 600 A (P1)
Indicates current in line 1
UNDER/OVER FREQUENCY
H8 lights up if generator frequency is above
illuminated pushbutton switch, red
or below setpoint; S4 cancels the fault mes-
(H8, S4)
sage
AMPS L2 (ØB) meter 0 - 600 A (P2)
Indicates current in line 2
UNDE/OVER VOLTAGE illumi-
H9 lights up if generator voltage is above or
nated pushbutton switch, red (H9, S5)
below setpoint; S5 cancels the fault message
GENERATOR OVER TEMPERA-
TURE illuminated pushbutton switch,
red (H10, S6)
H10 lights up if generator overheats;
S6 cancels the fault message
AMPS L3 (ØC) meter 0 - 600 A (P3)
Indicates current in line 3
OVERLOAD illuminated pushbutton
H13 lights up if generator overloads; S10
switch, red (H13, S10)
cancels the fault message
REVERSE POWER illuminated
H11 lights up if reverse power is too high;
pushbutton switch, red (H11, S22)
S22 cancels the fault message
Lights (H6)
For front panel illumination; use PANEL
DIMMER switch/potentiometer (33) to turn
on and adjust brightness
BATTERY CHARGING CONTROL
lamp, red (H2)
VOLTAGE meter 0 - 250 V (P6)
Indicates line or phase voltages L-L or L-N
OIL PRESSURE lamp, red (H3)
Must go out after start; if H3 lights up dur-
ing operation, oil pressure is too low
OIL TEMP-CYLINDER HEAD lamp,
Lights up when oil and/or cylinder head
red (H4)
temperature is too high
FREQUENCY meter, digital display
Displays generator frequency
(P5)
(400.0 ± 0.2 Hz during operation)
Function
Must go out after start; if H2 lights up dur-
ing operation, battery set is not being
charged